Technical Specifications
Low input current total harmonic distortion (THD)
Static and maintenance bypass switch
Output and by-pass short circuit and overload protection
192 events memory (192 events 4500 alarms)
Clock and calender (battery supported)
Automatic battery test, remaining battery time indicator
Temperature compansated charge system
Regenerative backfeed function
2 RS232 serial port and 12 dry contact outputs
3 DSP controlled modular structure
Optional Graphical and touch panel
CE, ISO9001, ISO14001 certification
2 years warranty
10 years spare parts support
Request infomation
Sản phẩm được sản xuất và nhập khẩu đồng bộ từ Châu Âu – Bảo hành 24 tháng – hỗ trợ linh kiện đến 10 năm.
    Hỗ trợ – Bảo vệ dự án
    Cung cấp đầy đủ các chứng từ nhập khẩu
    Đội ngũ kỹ thuật được đào tạo bài bản, có chứng chỉ hành nghề do nhà sản xuất cấp
    Sản phẩm được bảo trì 6 tháng / lần
    Hỗ trợ khảo sát – tư vấn giải pháp miễn phí
MODEL DSS3200T
Power(kVA) 200
INPUT
 Voltage 380/400 VAC 3P + N + G ± 20% ( 415 VAC + 15%, -25% optional)
Frequency 50 HZ /60Hz, ±5%
Power factor ≥ 0.99
 (THDI)(*) ≤ 3%
By-pass voltage 380/400 VAC 3Phase + N, 4 Wires, ±10%
Voltage distortion ≤ 10%
Protection Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequency indicatoer
OUTPUT
Power(kW) 180
Power Factor 0,9
 Voltage 380/400 VAC 3P + N, ± %1 ( 415 VAC optional) 
 Frequency 50Hz/60
Frequency tolerance Line synchronized: ±2% / Free running: ±0,1%
Efficiency up to 93%
Creast Factor 3:01
 Overload protection 100%-125%load:10 min, 125%-150% load1min, -> 150% load:by pass
Other protections Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THD <3%( at 100%linear load )
BATTERIES
Type VRLA AGM/GEL?NiCd 
Nominal voltage ± 312 VDC ( 2x26 batts)
Float/End of discharge voltage ± 351 VDC / ± 260 VDC
Battery cabinet External 
Battery ambient temperature 25ºC
Protections 3 level alarms, Battery fuses, charging current limit, Temperature compensation ( optional)
Automatic testing Standard every 72 hours (adjustable)
GENERAL
Standards EN62040-1, EN62040-2, EN62040-3
User interface 4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators P_N voltage P-P voltage, Current, Power, Crest factor, Frequency, PF, Service Time
Advanced Self diagnostics, 3 maintenance time indicators, Calobration over RS232, operating hour meter 
Communication 2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs EPO input, interactive battery panel input, Genset input
Genset kit Standard ( programmable)
Software Standard T-Mon UPS Management Software ( 3 clients + 1 server managerment)
Alarm loggging Standard: with time & date 512 events
Protections Power module over - temperature, Over current, Temperature high alarm
Temperature range 0ºC - 40ºC
 Protection degree IP20
Relative humidity 90%max ( non-condensing)
Altitude <1000m above sea level
Acoustic noise <57dBA
Weight (kg) 187
Dimensions (mm) HxWXD 1040x400x815
OPTION
Different input/output voltage Please ask
Software T-Mon admin Multi UPS Monitoring 10 – 50 – 100 – 200 Clients. T-Mon Server 50 – 100 – 200 clients
Adaptors SNMP, RS485, Remote monitoring panel, MODBUS ( RS485or TCP/IP), USB Alarm logger, TCP/IP, GSM?GPRS Modem, Com port multiplexer
Parallel Operations UP to 8

DOCUMENTATION